Wiring & Power Distribution
Macro
Micro
Cards
Layout
PID
Wiring
POWER TYPE LEGEND
3-phase-480V
Brown/Orange/Yellow
3-phase-208V
Black/Red/Blue
1-phase-240V
Black/Red
1-phase-120V
Black
24VAC
Red
24VDC
Red
3.3VDC
Orange
POWER DISTRIBUTION - SINGLE LINE DIAGRAM
UTILITY
480V 3Φ
400A Service
3x 500 MCM + G
MAIN DISTRIBUTION
MDP - Mechanical Room
Main Breaker:
400A
Bus Rating:
400A
AHU Supply VFD
40A | 8 AWG
AHU Exhaust VFD
30A | 10 AWG
Chiller
60A | 6 AWG
XFMR
ZONE PANEL
208V 3Φ
100A
Zone 1
240V 1Φ | 30A
Zone 2
240V 1Φ | 30A
Zone 3
240V 1Φ | 30A
Zone 4
240V 1Φ | 30A
CONTROL PANEL
24VDC / 3.3V
RPi
I2C
ADC
Power Panels
Main Distribution Panel
Mechanical Room
480V 3Φ
400A Main
Bus Rating
400A
Input Type
3-phase-480V
Circuits
4
BRANCH CIRCUITS
AHU Supply VFD
480V 3Φ
Breaker: 40A
Wire: 8 AWG
Conduit: 1"
Brown/Orange/Yellow
AHU Exhaust VFD
480V 3Φ
Breaker: 30A
Wire: 10 AWG
Conduit: 1"
Brown/Orange/Yellow
Chiller Compressor
480V 3Φ
Breaker: 60A
Wire: 6 AWG
Conduit: 1.25"
Brown/Orange/Yellow
Zone Panel Feed
208V 3Φ
Breaker: 125A
Wire: 1 AWG
Conduit: 2"
Black/Red/Blue
Zone Power Panel
Grow Room Corridor
208V 3Φ
100A Main
Control Panel
Control Room
120V 1Φ
30A Main
Important Notes
All 3-phase 480V circuits require proper PPE and lockout/tagout procedures
24VAC control circuits use Class 2 wiring methods per NEC Article 725
Low voltage DC circuits (3.3V/5V) are signal level and do not require conduit
Shielded cables required for analog signals to prevent EMI interference
I2C bus length should not exceed 3m without buffering